ENYECONTROLS Carbon Monoxide and Temperature Control & Monitoring System (EC-CMTCMS)

Designed to protect the building tenants/public from being exposed to Carbon Monoxide and monitor the temperature in each zone to minimize high-temperature readings for comfort.

Enyecontrols Carbon Monoxide & Temperature Control and Monitoring System (EC- CMTCMS) is designed to protect the building tenants/public from being exposed to Carbon Monoxide. Since Carbon Monoxide is colorless, odorless gas, it cannot be easily detected. It also monitors the temperature in each zone to minimize high temperature reading for comfort.

The specific function of the system is to provide comfort and enhance health safety in the enclosed basement parking by controlling and monitoring the carbon monoxide level and zone temperature.

The system shall automatically operate the transfer jet fans, exhaust and supply fans to satisfy the set points (35-50ppm for carbon monoxide and 30°C for temperature).

For efficiency and energy saving, the basement shall be divided into zones and only the specific zones with high concentration of carbon monoxide or high temperature shall be activated.

Advanced features which are also available in the system are as follows:

  1. Native BACnet for future BMS connection.
  2. LCD display and control functions at the central panel per floor.
  3. TCP/IP connection for laptop.
  4. USB connections to export/ save data stored in the controller.
  5. Also based on the carbon monoxide and temperature set points and upon sensing that transfer fans are activated, the exhaust and supply fans shall also be activated.
  6. Tolerance, set points can be changed and reprogrammed at the site if a better sequence, energy saving and operation protocol shall be decided based on actual operation as per instruction and approval of the owner/ consultants.
  7. All data such as temperature/ carbon monoxide readings/ set points, exhaust, transfer and supply fans on/off status shall be recorded in the Enyecontrols DDC Panel and can be extracted by the owner if necessary.
  8. Each Enyecontrols DDC Panel per basement shall have an FDAS fire alarm connection. In the event of fire, the system shall and can be programmed to perform either of the following:
    1. Turn off the supply fans, and turn on the exhaust and transfer fans.
    2. Turn off the supply fans and transfer fans, and turn on the exhaust fans.
    3. Program/customize the fire sequence, as deemed necessary.